21
Confi guration
AC POWER PANEL SURGE PROTECTOR
M Series
Model Confi guration
UL1449 3kA 8/20s (VPR)
Energy
(10/100us)
MCOV
L-N L-G N-G L-L
Mxxx-120T 120/240 Vac, 1 ph, 3 W+G, split phase 800 V 900 V 800 V 1800 V 3,240 J 150V
Mxxx-120Y 120/208 Vac, 3 ph, 4 W+G, wye 800 V 900 V 800 V 1800 V 4,680 J 150V
Mxxx-220Y 220/380 Vac, 3 ph, 4 W+G, wye 1200 V 1200 V 1200 V 2000 V 8,320 J 320V
Mxxx-240Y 240/415 Vac, 3 ph, 4 W+G, wye 1500 V 1200 V 1200 V 2000 V 8,320 J 320V
Mxxx-240DCT 120/240 Vac, 3 ph, 4 W+G, hi-leg 800 V 900 V 800 V 1800 V 6,080 J 150/320V
Mxxx-240D 240 Vac, 3 ph, 3 W+G, delta - 1200 V - 2000 V 7,680 J 320V
Mxxx-277Y 277/480 Vac, 3 ph, 4 W+G, wye 1500 V 1200 V 1200 V 2000 V 8,320 J 320V
Mxxx-347Y 347/600 Vac, 3 ph, 4 W+G, wye 1800 V 1800 V 1800 V 3000 V 12,480 J 550V
Mxxx-480D 480 vac, 3 ph, 3 W+G, delta - 1200 V - 2000 V 11,520 J 550V
Surge Handling (Imax) for :
M200 200kA/phase
M160 160kA/phase
M100 100kA/phase
M80 80kA/phase
Nominal Discharge Current (In) 3 kA & 5 kA
Protection Modes L-N, L-G, N-G, L-L
LED Indicators Yes
Audible Alarm Yes
Remote Signaling Form C dry contacts
Connecting Wire Size #10 AWG
Response Time < 5 nanoseconds
Dimensions 6’’ x 4’’ x 3.5’’
Enclosure NEMA 4/12 enclosure
Weight 8 lbs
Model
Dimensions (cm)
L h L' h'
M200
16 18.6 9 20.3
M160
M100
M80
xxx = 200, 160, 100, 80
Characteristics
• Imax from 80 to 200kA (8/20s)
• All mode of protection
• 200kAShort-circuit Fault Current Rated
• Multi-redundant protection circuit per phase
• Full On-Board Diagnostics - LED indicators,
remote & audible alarms
• EMI/RFI Noise Filtering
• NEMA 4/12 enclosure
• UL 1449 3ed. compliant
Dimensions
Catalogue Export.indd 21Catalogue Export.indd 21 28/09/11 10:0228/09/11 10:02